Role of hot water temperature and water system use on Legionella control in a tertiary hospital: An 8-year longitudinal study

Laura Gavaldà, Marian Garcia-Nuñez, Sara Quero, Carmen Gutierrez-Milla, Miquel Sabrià

Producción científica: Contribución a una revistaArtículoInvestigación

37 Citas (Scopus)

Resumen

Although measures to minimize Legionella colonization in sanitary hot water installations are well established, there is little evidence of their long-term effectiveness in hospital buildings. During an 8-year period, hot water in a large hospital building was sampled monthly in areas with suitable dimensioning and recirculation and in areas with dead legs and low-use taps. In the former areas, the percentage of Legionella-negative samples was 83.2% when the temperature was ≥55%, 64.9% when between 50.1 °C and 54.0 °C, and 51.6% when ≤50 °C (p for trend