Legionellosis has significant public health implications but is preventable via specific measures that are applied in hot water installations within hospitals. The impact of this disease on hospitalized patients is a significant problem, and these patients have substantially higher mortality than other cases acquired in the community. Minimizing Legionella colonization in sanitary hot water installations is frequently achieved by maintaining temperatures at minimum safety levels. However, legislations and technical guides disagree on the minimum required threshold: Spanish legislation sets this threshold at 50ºC; other countries set the limit at 55ºC. In addition to temperature, other factors that contribute to minimizing the proliferation of Legionella include the characteristics, uses and maintenance of sanitary hot water installations. However, the effectiveness of these measures remains to be proven in hospitals. _x000D_
The objectives of this thesis are to determine the long-term effectiveness of maintaining sanitary hot water at high temperatures as a single continuous disinfection method for Legionella in a hospital and to describe the genotypic variability of Legionella as a function of the factors associated with each installation. For the first objective, an 8-year intervention study compared the sanitary hot water cultures obtained in two periods: a first period in which the lowest required temperature was 50ºC, and a second period in which that temperature was increased to 55ºC. For the second objective, a descriptive study of genotypic patterns identified in cryopreserved isolates of Legionella was conducted using pulsed field electrophoresis._x000D_
The findings of this thesis indicate that the effectiveness of maintaining sanitary hot water at a minimum temperature of 55ºC is significantly better than that at 50ºC for the environmental control of Legionella but only in installations with suitable dimensioning and recirculation. In installations that do not meet these conditions, high temperatures alone result in insufficient control. The presence of Legionella in this type of installation is significantly associated with a low frequency of installation use. A molecular characterization showed low genotypic variability of Legionella in sanitary hot water with a varying predominant pattern according to each independent installation within one building. One of the major patterns is predominant in samples with high temperatures. _x000D_
The findings of this thesis provide new evidence for the prevention of legionellosis. In particular, the importance of properly monitoring the temperature of sanitary hot water as a basic continuous disinfection method should be emphasized. Installations should ensure proper recirculation and not utilize dead or infrequently used installations. Finally, the molecular characterization of Legionella is herein shown to be a useful tool for the management of the environmental risks associated with sanitary water.
EFECTIVIDAD A LARGO TÉRMINO DE LA TEMPERATURA COMO MÉTODO DE CONTROL DE LEGIONELLA EN AGUA CALIENTE SANITARIA
Gavalda Mestre, L. (Author). 19 Dec 2016
Student thesis: Doctoral thesis
Gavalda Mestre, L. (Author),
Sabria Leal, M. (Director),
19 Dec 2016Student thesis: Doctoral thesis